MBW Sf6

Electrical Engineering & Consulting Belgium  Sprl                                                                                                                                                            

   122 Avenue Louis Bertrand                                                        Contact        Pierre Culot

         B 1030 Bruxelles                                                             Mobile        +32 (0) 477 27 88 04

             Belgique                                                                   email          info@eecsprl.be

     

          Hexaflurure de soufre   Sf6


- Gaz incolore, inodore et insipide

- Gaz stable à haute capacité de dissipation thermique

- Molécule 5 fois plus lourde qu'une molécule d'air

- Gaz non toxique, non inflammable et insoluble dans l'eau

- Gaz isolant dans les équipements à haute tension

- Gaz  souffleur d'arc dans le compartiment

      disjoncteur


- Gaz à effet de serre, une molécule de Sf6 est  22.800

    fois plus polluante que la molécule de CO2.


- Gaz soumis au Protocole de Kyoto de 2005 et ratifié par

  156 pays.


Gaz soumis au respect des normes européennes  n°


                                  EC 842/2006 du 17 mai 2006

                                  EC 305/2008 du 2 avril 2008

                                  EC 517/2014  du 16 avril 2014

ANALYSE DU GAZ DANS VOS INSTALLATIONS GIS ou tout équipement comportant du GAZ  (Disjoncteur)

Pointsde rosée, % Sf6,  Pression, et SO2.


Mesures effectuées avec  MBW Sf6 Analyser type 973


Représentation de MBW en Belgique.


Mise à disposition de l'appareil pour effectuer vos mesures. Location par semaine


www.mbw.ch

Features


- Simultaneous measurement of humidity, Sf6 purity and SO2 concentration.

- Integrated gas recovery system with automatic pump back.

- Fully automated Sf6 gas testing.

- Fundamental drift-free measuring principle

- Measurement results at Sf6 compartment or standard pressure.

- Intuitive color touch screen user interface.

- User verifiable calibration.

- Robust case for easy transportation.


Optimum Sf6 Gas Analysis Solution


- The 973 Sf6 is an advanced analyzer for the measurement of humidity, Sf6 purity and SO2 concentration in Sf6 gas insulated switchgears (GIS) and other high voltage equipment. With its internal gas containment and recovery system, the 973 Sf6 provides a high quality and environmentally safe measurement solution within a single, self-contained unit. Pure Sf6 is the standard filling within GIS , but over time gas compartments become contaminated with vapor (H2O) through permeation and by desorption from internal components.


- Whilst water vapor and Sf6 do not normally react with each other, in the presence of high-energy discharge, hydrogen and oxygen disassociated from water vapor will react with the sulfur and fluorine from Sf6 to from decomposition by-products. These included sulfur dioxide (SO2) and hydrofluoric acid (HF) that are the corrosive to the internal components of gas compartments.


-Sf6 with low wter vapor content (low humidity) significantly reduces the potential for formation of these corrosive compounds, which is xhy accurate and repeatable measurement data is an invaluable part of any GIS preventative maintenance program.


- Put simply, careful maintenance of the quantity of water vapor within  Sf6 gas insulated equipment is key to equipment reliability and minimized costs. The 973-Sf6 gives the user the best possible measument capability with low operating costs and no release of Sf6 gas.



SERVICES et MAINTENANCES


Sur simple demande, nous analysons l'état du gaz Sf6 de vos installations.

Assistance extraction et traitement du Gaz Sf6 suivant normes Kyoto.